IEC 298 12KV Medium Voltage Ring Main Unit Switchg
IEC 298 12KV Medium Voltage Ring Main Unit Switchgear IP2X
PRODUCT NAME: | Ring Main Unit Switchgear Air Insulated Switchgear | RATED VOLTAGE: | 12KV |
APPLICATION: | Indoor | RATED FREQUENCY: | 50Hz |
DEGREE OF PROTECTION | IP2X | STANDARD: | IEC 298 |
Product introduction , HXGN11-12
Cubicle Fixed Indoor AC Metal-clad Ring Main Unit Switchgear ( "RMU") is a latest version of high voltage equipment by absorbing and digesting advanced technology in domestic and abroad, specially suitable for municipal power supply net of improvement and reconstruction. After a model approval test and a long-term running test, this product is certified to meet IEC298 standard Alternative Current Metal-clad Switchgear. Protection level of the product comes up to IP2X. It features small volume, light-weight, easy operation, small operative force, safety, easy maintenance, stable and reliable quality, free of fire disaster or explosion disaster, close to wall installation, small area occupied, etc. And if required, a three-phases coupling function could be satisfied.
RMU with three phases, 10kV rated voltage, 50Hz rated frequency, is suitable for power transmission and distribution system in places such as factory or mining enterprise, residential zone, high building, school, park, etc. It could also be used in ring net or terminal power supply.
Service condition
a. Altitude≤1000m
b. Ambient air temperature: Maximum +40ºC Minimum -35ºC
c. Relative humidity: Diary average value shall be not more than 95%; monthly average value shall be not more than 90%
d. Ambient air should be with no corrosion, no apparent pollution with combustible gas and etc.
e. Earthquake prevent function: process ground horizontal acceleration 0.2g and vertical acceleration0.1g at the same time, adopt resonance, sine, whip wave test, safety factor should be more than 1.67
Technical parameter of Ring Main Unit Switchgear Air Insulated Switchgear, HXGN11-12
S/N | Description | Unit | Data |
1 | Rated voltage | kV | 12 |
2 | Rated frequency | Hz | 50 |
3 | Rated current of main busbar | A | 630 |
4 | Rated short-time withstand current of main circuit, earth circuit | kA/s | 25/2 |
5 | Rated peak withstand current of main circuit, earth circuit | kA/s | 63 |
6 | Rated short circuit making current of main circuit, earth circuit | kA/s | 63 |
7 | LBS full capacity breaking times | times | 100 |
8 | Fuse breaking current | kA/s | 31.5 40 |
9 | Mechanical endurance | times | 10000 |
10 | 1 min power frequency withstand voltage | ||
phase to earth | kV | 42 | |
phase to phase/ between isolating clearance | kV | 48 | |
11 | Lightning impulse withstand voltage (peak) | ||
phase to earth | kV | 75 | |
phase to phase/ between isolating clearance | kV | 85 | |
12 | 1 min power frequency withstand voltage of Secondary circuit | kV | 2 |
Product Categories : Ring Main Unit RMU > Gas-insulated Ring Main Unit
Mr. simon.tang
Tel:
86-519-85131880
Fax:
86-519-85131880
E-mail:
Privacy statement: Your privacy is very important to Us. Our company promises not to disclose your personal information to any external company with out your explicit permission.
Fill in more information so that we can get in touch with you faster
Privacy statement: Your privacy is very important to Us. Our company promises not to disclose your personal information to any external company with out your explicit permission.