Model No.: 6NTA
Brand: TRANCHART
Transportation: Ocean,Land
Place of Origin: Changzhou
Port: Shanghai,Ningbo
Payment Type: L/C,T/T
6NTA Series Air 400-600V Circuit Breaker
6NTA series frame circuit breaker is suitable for AC 50/60Hz, rated working voltage 415V/690V power supply and distribution network, used to distribute electrical energy and protect lines and power equipment from overload, undervoltage, short circuit, grounding and other hazards. The circuit breaker adopts precise selective protection and multi-functional intelligent controller, complete protection and communication functions.
In ORDER to improve the reliability of power supply and avoid unnecessary power failure, intelligent controller with communication interface can be selected. Through field bus connection, telemetry, remote control, remote signal four remote functions can be achieved to meet the requirements of intelligent distribution network.
The series products have passed the type test earthquake test and anti-fault arc test in China and KEMA. The design meets the electrical industry standards of IEC,DIN,ASTM,GB,etc.,and can meet the power supply and operation requirements of domestic and foreign markets to ensure product operation reliability and operator safety.
Technical Parameters
Type | 6NTA-16 | 6NTA-25 | 6NTA-40 | ||||||
Frame rated current | 1600 | 2500 | 4000 | ||||||
Inm(A) | |||||||||
Rated current In(A) | 400,630,800, | 630,800,1000,1250, | 2000,2500,2900, | ||||||
100,012,501,600 | 2000,2500, | 3200,3600,,4000 | |||||||
Rated insulation voltage Ui(V) | 1000 | ||||||||
Rated frequency(HZ) | 50/60 | ||||||||
Rated impulse withstand voltage Uimp (kV) | 12 | ||||||||
Pole number | 3P/4P | ||||||||
Rated current of neutral pole IN | 100%In | ||||||||
Breaking capacity | N | H | N | H | S | H | S | V | |
Rated limit short circuit breaking capacity Icu(kA) | AC415V | 50 | 65 | 50 | 65 | 85 | 65 | 85 | 100 |
AC690V | 30 | 50 | 40 | 50 | 65 | 50 | 65 | 85 | |
Rated running short circuit breaking capacity Ics(kA) | AC415V | 50 | 55 | 50 | 65 | 85 | 65 | 85 | 100 |
AC690V | 30 | 50 | 40 | 50 | 65 | 50 | 65 | 85 | |
Rated short circuit making | AC415V | 105 | 143 | 105 | 143 | 187 | 143 | 187 | 220 |
capacity Icm (peak value)(kA) | AC690V | 55 | 105 | 84 | 121 | 143 | 121 | 143 | 187 |
Rated short time withstand current 1cw, | AC415V | 50/1S | 55/1S | 50/1S | 65/1S | 85/1S | 65/1S | 85/1S | 100/1S |
30/3S | 50/3S | 65/3S | |||||||
AC690V | 30/1S | 50/1S | 40/1S | 50/1S | 65/1S | 50/1S | 65/1S | 85/1S | |
30/3S | 40/3S | 50/3S | |||||||
Mechanical endurance | 12000 | 12000 | 8000 | ||||||
Electrical endurance | 6500 | 8000 | 6000 |
Product Categories : Circuit Breaker > Intelligent Universal Circuit Breakers
Mr. simon.tang
Tel:
86-519-85131880
Fax:
86-519-85131880
E-mail:
Privacy statement: Your privacy is very important to Us. Our company promises not to disclose your personal information to any external company with out your explicit permission.
Fill in more information so that we can get in touch with you faster
Privacy statement: Your privacy is very important to Us. Our company promises not to disclose your personal information to any external company with out your explicit permission.