12KV 630-2000A Vacuum VCB Circuit Breaker Withdrawable High Stability
Voltage: | 12-24KV | Current: | 630-2000A |
Breaking Current: | 25KA Max | Type: | Withdrawable |
Standard: | GB,ISO,IEC |
VS1-Series circuit breaker features high stability and high reliability
"High-Voltage Vacuum Circuit Breaker" is named because both the arc extinguishing medium and the insulating medium of the contact gap after arc extinguishing are vacuum; Advantages, the application in the distribution network is more popular.
The circuit breaker is identified by some national standards and international relative standards, such as GB1984,GB/T11022,DL/T403 and IEC62271, etc.
Service Condition
Altitude ≤1000m Ambient temperature Max +40℃ Min -15℃ Ambient humidity: 24 hours ≤95% Maximum average humidity 1 month ≤90% Maximum water vapor pressure 24 hours ≤2.2kpa 1 month ≤1.8kpa
Technical Parameters
No. | Item | Unit | Parameter | ||||||
1 | Rated voltage | KV | 12 | ||||||
2 | Rated frequency | Hz | 50/60 | ||||||
3 | 1min power frequency withstand voltage(r. m. s) | 42(phase-to-phase, phase-to-earth) | |||||||
Rated insulation level | KV | 48(across the isolating distance) | |||||||
Lighting impulse withstand voltage (peak) | 75(phase-to-phase, phase-to-earth) | ||||||||
85(across the isolating distance) | |||||||||
630 | 630 | 1250 | 1600 | ||||||
1250 | 1250 | 1600 | 2000 | ||||||
4 | Rated current | A | 2000 | 2500 | |||||
2500 | 3150 | ||||||||
4000 | |||||||||
5 | Rated short-circuit breaking current | 20 | 25 | 31.5 | 40 | ||||
6 | Rated short-time withstand current | KA | 20 | 25 | 31.5 | 40 | |||
7 | Rated short-circuit marking current | 50 | 63 | 80 | 100 | ||||
8 | Rated peak withstand current | 50 | 63 | 80 | 100 | ||||
9 | Rated duration of short-circuit | s | 4 | ||||||
10 | Rated operating sequence | O-0.3s-O/C-180s-O/C | |||||||
11 | Breaking times of rated short-circuit current | Times | 30/20 times(40KA) | ||||||
12 | Mechanical endurance | Ops | 20000 | ||||||
13 | Rated single capacitor bank breaking current | 630 | |||||||
14 | Rated back-to-back capacitor bank breaking current | A | 400 | ||||||
15 | Double-earth fault breaking current | 27.4 | |||||||
16 | Allowable maximum contact erosion | 3 | |||||||
17 | Clearance between open contacts | mm | 10±1 | ||||||
18 | Over stroke | 3.5±0.5 | |||||||
19 | Non-simultaneity of 3-phase opening and closing | ms | ≤2 | ||||||
20 | Bounce duration of contact closing | ≤2 | |||||||
21 | Average breaking speed (instant breaking 6mm) | m/s | 1.1±0.2 | ||||||
22 | Average making speed | 0.8±0.2 | |||||||
23 | Making time | ms | ≤100 | ||||||
24 | Breaking time | ≤50 | |||||||
630A | ≤50 | ||||||||
Resistance of each phase main circuit | μ Ω | 1250A | ≤45 | ||||||
25 | 1600A~2000A | ≤35 | |||||||
≥2500A | ≤25 | ||||||||
26 | Contact breaking bounce amplitude | mm | ≤2 | ||||||
Rated operating voltage | Rated operating voltage(V)AC/DC | 24* | 110 | 220 | |||||
27 | Scope of normal operation voltage | V | Opening:65%-120% rated voltage, in case the voltage is lower than 30% rated voltage, opening operation is not allowed | ||||||
28 | Rated voltage of energy storage motor | V | AC110/220,DC110/220 | ||||||
29 | Energy storage time | S | ≤15 |
Product Categories : Circuit Breaker > High-Voltage Vacuum Circuit Breaker
Mr. simon.tang
Tel:
86-519-85131880
Fax:
86-519-85131880
E-mail:
Related Products List
Mobile Site
Privacy statement: Your privacy is very important to Us. Our company promises not to disclose your personal information to any external company with out your explicit permission.
Fill in more information so that we can get in touch with you faster
Privacy statement: Your privacy is very important to Us. Our company promises not to disclose your personal information to any external company with out your explicit permission.